The A9N18358 Miniature Circuit Breaker by Schneider Electric – Your Compact Circuit Guardian!
Are you in search of a reliable circuit protection solution for your electrical systems? Look no further! The A9N18358 Miniature Circuit Breaker from Schneider Electric is designed to keep your circuits safe and your electrical installations running smoothly.
Key Features:
Single-Pole Design: This 1P circuit breaker offers compact and efficient protection.
High Amperage Rating: With a 100A rating, it's capable of handling various electrical loads.
C-Curve: Designed to quickly trip in case of a short circuit, ensuring enhanced protection.
Impressive Breaking Capacity: With a 10 kA IEC 60898-1 and 10000A IEC 60947-2 breaking capacity, it can handle high fault currents.
User-Friendly: Its compact design makes installation and operation hassle-free.
Durable Build: Crafted to last, providing longevity and dependability in your electrical system.
The A9N18358 Miniature Circuit Breaker is engineered to meet your circuit protection needs, offering peace of mind and uninterrupted performance. Whether for residential or industrial use, its compact design and impressive specifications make it the ideal choice.
Elevate your electrical systems with the A9N18358 Miniature Circuit Breaker and enjoy enhanced safety and reliability!
Specifications: | |
Main |
|
Range of product | C120 |
Range | Acti9 |
Product name | C120 |
Product or component type | Miniature circuit-breaker |
Device short name | C120N |
Device application | Distribution |
Poles description | 1P |
Number of protected poles | 1 |
[In] rated current | 100 A at 30 °C |
Network type | AC |
Trip unit technology | Thermal-magnetic |
Curve code | C |
Breaking capacity | 3 kA Icu at 380...415 V AC 50/60 Hz IT conforming to EN/IEC 60947-2 |
20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 | |
15 kA Icu at 12 V DC conforming to EN/IEC 60947-2 | |
15 kA Icu at 125 V DC conforming to EN/IEC 60947-2 | |
10 kA Icu at <= 144 V DC conforming to EN/IEC 60947-2 | |
10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 | |
20 kA Icu at 12 V AC 50/60 Hz conforming to EN/IEC 60947-2 | |
10000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1 | |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Complementary | |
Network frequency | 50/60 Hz |
[Ue] rated operational voltage | 380...415 V AC 50/60 Hz |
125 V DC | |
<= 144 V DC | |
12 V DC | |
220...240 V AC 50/60 Hz | |
230...400 V AC 50/60 Hz | |
130 V AC 50/60 Hz | |
12 V AC 50/60 Hz | |
Magnetic tripping limit | 5...10 x In |
[Ics] rated service breaking capacity | 15 kA 75 % conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz |
15 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC | |
2.25 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz | |
15 kA 100 % conforming to EN/IEC 60947-2 - 12 V DC | |
10 kA 100 % conforming to EN/IEC 60947-2 - <= 144 V DC | |
7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz | |
15 kA 75 % conforming to EN/IEC 60947-2 - 12 V AC 50/60 Hz | |
7500 A 75 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz | |
Limitation class | 3 conforming to EN/IEC 60947-2 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
Contact position indicator | Yes |
control type | Toggle |
Local signalling | ON/OFF indication |
Mounting mode | Clip-on |
mounting support | 35 mm symmetrical DIN rail |
Comb busbar and distribution block compatibility | YES |
9 mm pitches | 3 |
height | 81 mm |
Width | 27 mm |
Depth | 73 mm |
Net weight | 0.205 kg |
Colour | White |
Mechanical durability | 20000 cycles |
Electrical durability | 5000 cycles conforming to IEC 60947-2 |
Locking options description | Handle sealable with cable diameter 0.7mm in OFF or ON position |
Connections - terminals | Tunnel type terminals1…50 mm² rigid |
Tunnel type terminals1.5…35 mm² flexible | |
Wire stripping length | 15 mm |
Tightening torque | 3.5 N.m |
earth-leakage protection | Without |
Environment | |
standards | EN/IEC 60898-1 |
EN/IEC 60947-2 | |
product certifications | EAC |
IP degree of protection | IP20 conforming to IEC 60529 |
Pollution degree | 3 conforming to IEC 60947-2 |
Overvoltage category | IV |
Tropicalisation | 2 conforming to IEC 60068-1 |
Relative humidity | 95 % at 55 °C |
Operating altitude | 2000 m |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -40…85 °C |