Acti9 iC60N 32 A Miniature Circuit Breaker 1P, C curve, Schneider Electric
Poles description: 1P
Number of protected poles: 1
[In] rated current: 32 A
Network type: AC, DC
Curve code: C
The Schneider Electric A9F77132 Acti9 IC60N Miniature Circuit Breaker is a reliable and compact solution designed for circuit protection. With a single-pole configuration and a 32 A current rating, this C-curve circuit breaker is suitable for various applications. It offers a high breaking capacity of 6000 A according to IEC 60898/1 and has a 10 kA short-circuit breaking capacity per IEC 60947-2. Ensure the safety of your electrical circuits with this high-quality circuit breaker.
Key Features:
Single-Pole Configuration: Designed as a single-pole circuit breaker.
Current Rating: Rated at 32 A, suitable for various electrical circuits.
C Curve: The C curve characteristic provides effective protection for circuits.
High Breaking Capacity: Offers a high breaking capacity of 6000 A according to IEC 60898/1.
Short-Circuit Protection: 10 kA short-circuit breaking capacity per IEC 60947-2.
Technical Specifications:
-
Current Rating: 32 A
-
Operation Type: C Curve
-
Number of Poles: 1
-
Breaking Capacity: 6000 A IEC 60898/1, 10 kA IEC 60947-2
The Schneider Electric A9F77132 Acti9 IC60N Miniature Circuit Breaker is a fundamental component for safeguarding electrical circuits.
Specifications | |
Main | |
Device application | Distribution |
Range | Acti9 |
Product name | Acti9 iC60 |
Product or component type | Miniature circuit-breaker |
Device short name | IC60N |
Poles description | 1P |
Number of protected poles | 1 |
[In] rated current | 32 A |
Network type | DC |
AC | |
Trip unit technology | Thermal-magnetic |
Curve code | C |
Breaking capacity | 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 | |
15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 | |
10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 | |
36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 | |
20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 | |
Utilisation category | Category A conforming to EN 60947-2 |
Category A conforming to IEC 60947-2 | |
Suitability for isolation | Yes conforming to EN 60898-1 |
Yes conforming to EN 60947-2 | |
Yes conforming to IEC 60898-1 | |
Yes conforming to IEC 60947-2 | |
standards | IEC 60898-1 |
IEC 60947-2 | |
EN 60898-1 | |
EN 60947-2 | |
Quality labels | NF |
Complementary | |
Network frequency | 50/60 Hz |
Magnetic tripping limit | 8 x In +/- 20 % |
[Ics] rated service breaking capacity | 27 kA 75 % conforming to EN 60947-2 - 12...60 V AC 50/60 Hz |
7.5 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz | |
27 kA 75 % conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz | |
7.5 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz | |
15 kA 75 % conforming to IEC 60947-2 - 100...133 V AC 50/60 Hz | |
15 kA 75 % conforming to EN 60947-2 - 100...133 V AC 50/60 Hz | |
6000 A 100 % conforming to EN 60898-1 - 230 V AC 50/60 Hz | |
6000 A 100 % conforming to IEC 60898-1 - 230 V AC 50/60 Hz | |
10 kA 100 % conforming to EN 60947-2 - 72 V DC | |
10 kA 100 % conforming to IEC 60947-2 - 72 V DC | |
15 kA 100 % conforming to EN 60947-2 - 12...60 V DC | |
15 kA 100 % conforming to IEC 60947-2 - 12...60 V DC | |
Limitation class | 3 conforming to EN 60898-1 |
3 conforming to IEC 60898-1 | |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN 60947-2 |
500 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN 60947-2 |
6 kV conforming to IEC 60947-2 | |
Contact position indicator | Yes |
control type | Toggle |
Local signalling | Trip indicator |
Mounting mode | Fixed |
mounting support | DIN rail |
Comb busbar and distribution block compatibility | Top or bottom: YES |
9 mm pitches | 2 |
height | 85 mm |
Width | 18 mm |
Depth | 78.5 mm |
Net weight | 0.215 kg |
Colour | White |
Mechanical durability | 20000 cycles |
Electrical durability | 10000 cycles |
Connections - terminals | Single terminal (top or bottom) 1…35 mm² rigid |
Single terminal (top or bottom) 1…25 mm² flexible | |
Wire stripping length | 14 mm for top or bottom connection |
Tightening torque | 3.5 N.m top or bottom |
earth-leakage protection | Without |
Environment | |
IP degree of protection | IP20 conforming to IEC 60529 |
IP20 conforming to EN 60529 | |
Pollution degree | 3 conforming to EN 60947-2 |
3 conforming to IEC 60947-2 | |
Overvoltage category | IV |
Tropicalisation | 2 conforming to IEC 60068-1 |
Relative humidity | 95 % at 55 °C |
Operating altitude | 0...2000 m |
Ambient air temperature for operation | -35…70 °C |
Ambient air temperature for storage | -40…85 &de |
Brand | Schneider Electric |
---|---|
Depth [cm] | 7.85 |
Width [cm] | 1.8 |
Height [cm] | 8.5 |