Compact NSX250F Circuit Breaker, 36kA at 415V AC, Micrologic 2.2 Trip Unit, 160A, 3 Poles, 3D

In stock
SKU
C25F32D160
Special Price EGP 29,804 Regular Price EGP 45,157

Details

The C25F32D160 Compact NSX250F Circuit Breaker is a high-quality electrical circuit protection device designed for use in the Compact NSX250F series. This circuit breaker offers reliable protection for electrical circuits and comes equipped with advanced features for optimal performance. It is suitable for a wide range of applications, providing a comprehensive solution for circuit control and protection.

 

Key Features:

Compact Design: The Compact NSX250F series is known for its space-saving design, making it suitable for various installation environments.

High Breaking Capacity: With a breaking capacity of 36kA at 415V AC, this circuit breaker can safely disconnect short circuits, ensuring the protection of electrical systems.

3 Poles: The circuit breaker features three poles, making it versatile for applications requiring multiple circuits or phases.

Micrologic 2.2 Trip Unit: Equipped with a Micrologic 2.2 trip unit, this circuit breaker offers precise protection against overloads and short circuits.

160A Rating: With a current rating of 160A, this circuit breaker can efficiently handle electrical loads.

 

Whether you need reliable protection for industrial, commercial, or residential applications, the C25F32D160 circuit breaker is a trusted choice. It ensures the safety of your electrical systems and helps prevent damage from overloads and short circuits.

 

Specifications

 

Main

 
Range ComPacT new generation
Product name ComPacT NSX new generation
device short name NSX250F
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3D
[In] rated current 160 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
  36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
  35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
  22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
  8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
  35 kA at 480 V AC 50/60 Hz conforming to UL 508
  15 kA at 600 V AC 50/60 Hz conforming to UL 508
Performance level F 36 kA 415 V AC
Trip unit name MicroLogic 2.2
Trip unit technology Electronic
Trip unit protection functions LSoI
control type Toggle
Circuit breaker mounting mode Fixed
Complementary  
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service short-circuit breaking capacity 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
  36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
  35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
  30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
  22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
  8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles
Electrical durability 20000 cycles at 440 V In/2
  10000 cycles at 440 V In
  10000 cycles at 690 V In/2
  5000 cycles at 690 V In
Power dissipation per pole 7.17 W
mounting support Backplate
Mounting position Horizontal and vertical
  Flat on the back
Upside connection Front
downside connection Front
Connection pitch 35 mm
Protection type L : for overload protection (long time)
  So : for short time short-circuit protection with fixed delay
  I : for instantaneous short-circuit protection
Trip unit rating 160 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range 63...160 A
Long-time protection delay adjustment type tr Fixed
[tr] long-time protection delay adjustment range 400 s at 1.5 x Ir
  16 s at 6 x Ir
  11 s at 7.2 x Ir
thermal memory 20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range 1.5...10 x Ir
Short-time protection delay adjustment type tsd Fixed
Instantaneous protection pick-up adjustment type Ii Fixed
[Ii] instantaneous protection pick-up adjustment range 2400 A
earth-leakage protection Without
Zone selective interlocking ZSI Without
Number of slots for electrical auxiliaries 5 slot(s)
Local signalling Flashing LED (green) for ready to operate
  LED 105 % Ir (red) for overload
  LED 90 % Ir (orange) for overload
Width (W) 105 mm
Height (H) 161 mm
Depth (D) 86 mm
Net weight 2.4 kg
Environment  
standards EN/IEC 60947
product certifications CCC
  Marine
  EAC
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating
  2000 m...5000 m with derating

 

 

More Information

More Information
Brand Schneider Electric
Depth [cm] 8.6
Width [cm] 10.5
Height [cm] 16.1

Reviews

You're reviewing: