Schneider Electric Tesys F Contactor, 3P, 3-NO, AC3, 440V, 150A, Coil 220V AC
Range of product: TeSys
Product type: Contactor
Poles: 3P
contactor application: Resistive load, Motor control
The Schneider Electric LC1F150M7 is a high-performance contactor from the Tesys F series, designed for reliable and efficient control of electrical circuits. With three poles and a current rating of 150 A at AC-3, this contactor is capable of handling heavy-duty applications. It features a 220V AC coil for easy activation and deactivation of the contactor. The contactor is rated for 440V AC-3 applications, making it suitable for a wide range of industrial and commercial uses.
Key Features:
Heavy-Duty Performance: The LC1F150M7 contactor is built to handle heavy loads and is ideal for demanding applications.
Three Poles: This contactor is designed with three poles, making it suitable for three-phase systems.
Coil Voltage: The 220V AC coil voltage ensures efficient control and operation.
Rated for 440V AC-3: This contactor is rated for 440V AC-3 applications, making it versatile for various industrial uses.
Product Specifications:
Poles: 3P (Three Poles)
Current Rating: 150 A (AC-3)
Coil Voltage: 220V AC
Rated Voltage (AC-3): 440V
Specifications
Main | |
Range | TeSys |
Range of product | TeSys F |
Product or component type | Contactor |
Device short name | LC1F |
contactor application | Resistive load |
Motor control | |
utilisation category | AC-3 |
AC-1 | |
AC-4 | |
Poles description | 3P |
[Ue] rated operational voltage | <= 690 V AC 50/60 Hz |
<= 460 V DC | |
[Uc] control circuit voltage | 220 V AC 40...400 Hz |
[Ie] rated operational current | 250 A (at <40 °C) at <= 440 V AC-1 |
150 A (at <55 °C) at <= 440 V AC-3 | |
Complementary | |
[Uimp] rated impulse withstand voltage | 8 kV |
[Ith] conventional free air thermal current | 250 A (at 40 °C) |
Rated breaking capacity | 1200 A conforming to IEC 60947-4-1 |
[Icw] rated short-time withstand current | 1200 A 40 °C - 10 s |
700 A 40 °C - 30 s | |
600 A 40 °C - 1 min | |
450 A 40 °C - 3 min | |
350 A 40 °C - 10 min | |
Associated fuse rating | 160 A aM at <= 440 V |
250 A gG at <= 440 V | |
Average impedance | 0.35 mOhm - Ith 250 A 50 Hz |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 |
1500 V conforming to VDE 0110 group C | |
Power dissipation per pole | 22 W AC-1 |
8 W AC-3 | |
Overvoltage category | III |
power pole contact composition | 3 NO |
Motor power kW | 75 kW at 380...400 V AC 50/60 Hz (AC-3) |
80 kW at 415 V AC 50/60 Hz (AC-3) | |
80 kW at 440 V AC 50/60 Hz (AC-3) | |
90 kW at 500 V AC 50/60 Hz (AC-3) | |
100 kW at 660...690 V AC 50/60 Hz (AC-3) | |
40 kW at 220...230 V AC 50/60 Hz (AC-3) | |
22 kW at 400 V AC 50/60 Hz (AC-4) | |
Control circuit voltage limits | Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) |
Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C) | |
Mechanical durability | 10 Mcycles |
Inrush power in VA | 770 VA, 40...400 Hz cos phi 0.9 (at 20 °C) |
Hold-in power consumption in VA | 8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C) |
Maximum operating rate | 2400 cyc/h 55 °C |
Operating time | 35 ms closing (at Uc) |
130 ms opening (at Uc) | |
Connections - terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end |
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end | |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end | |
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end | |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end | |
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end | |
Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm | |
Power circuit: lugs-ring terminals 1 cable(s) 120 mm² | |
Power circuit: connector 1 cable(s) 120 mm² | |
Power circuit: bolted connection | |
Tightening torque | Control circuit: 1.2 N.m |
Power circuit: 18 N.m | |
mounting support | Plate |
Heat dissipation | 5.9…7.2 W |
standards | EN 60947-4-1 |
EN 60947-1 | |
IEC 60947-4-1 | |
JIS C8201-4-1 | |
IEC 60947-1 | |
product certifications | BV |
RINA | |
LROS (Lloyds register of shipping) | |
RMRoS | |
ABS | |
CCC | |
CB | |
UL | |
DNV | |
UKCA | |
Compatibility code | LC1F |
Control circuit type | AC at 40...400 Hz |
Environment | |
IP degree of protection | IP2X front face with shrouds conforming to IEC 60529 |
IP2X front face with shrouds conforming to VDE 0106 | |
Protective treatment | TH |
Ambient air temperature for operation | -40…60 °C |
Ambient air temperature for storage | -60…80 °C |
Permissible ambient air temperature around the device | 60…70 °C at Uc |
height | 170 mm |
Width | 163.5 mm |
Depth | 171 mm |
Operating altitude | 3000 m without derating |
Net weight | 3.43 kg |
Brand | Schneider Electric |
---|---|
Depth [cm] | 17.1 |
Width [cm] | 3.43 |
Height [cm] | 17 |